Other MPP-Related Changes
- The team needs to work to update the system drawing and generate a valve schedule for each operating configuration and condition, including, at a minimum, any time when cooling tower component(s) are brought online.
- The Risk Management Assessment needs to be updated to include operating configurations and conditions that may result in low flow or no flow in any part of the system.
- The MPP must be certified annually by the plan preparer.
- A new log sheet will be created for tracking reactions to dip slide counts greater than or equal to 10,000 CFUs/mL.
- Cooling towers may only be supplied by a municipal water supply. If water from a non-potable water source is used, the owner must submit an alternative water source plan (AWSP).
- That AWSP is a separate plan that must identify each non-potable water source and include provisions for adequate design of treatment and control components and ongoing evaluation to eliminate any risk to public health.
- That AWSP must be approved by the DOH before any non-potable water source can be used for cooling tower make-up.
Additionally, seven new violations have been added, and all existing violations have doubled in cost (both for a first violation and for repeat violations), ranging from $1,000-$4,000 per citation.
|