Sunday News

August 11, 2024

CEO: Gayle Nash, MPH, RN

COO/CFO: Sam Sheth, PharmD, MBA

Contracts Manager: Kristin Miller, JD

CEO Corner


Hi all, I hope you had a good week. 


We have had a busy summer addressing sterile processing and instrument issues, physical environment findings related to sterilizers, and water and pressure relationships. This week, we are continuing our three-part series on the physical environment. 


In keeping with the environment of care and life safety theme, I am sending along Joint Commission's Frequently Asked Questions that seem to be a frequent topic of discussion. In addition, you will find a publication on the Red Cross blood shortage, ISMP monthly update for acute care, and a flu vaccine update. Once again, if you have requests, I will do the research for you. 


Our engineer who authored this article is Harold Blits, BS, CHSP. Harold has thirty years of experience in clinical and administrative healthcare roles in environment of care, life safety, and accreditation, he earned his Bachelor of Science in Fire Science and Safety Engineering, and he is a member of the American Society of Hospital Engineers, a Certified Healthcare Safety Professional, and NFPA – CLSS. Harold is also a critical care paramedic, a firefighter, and a member of the Kansas Incident Management Team (IMT) for disaster response.  

 

Frequently Cited Chapters in the Physical Environment


On July 1, 2023, The Joint Commission made significant updates to the Emergency Management (EM) standard for home care, aiming to create a more comprehensive and aligned EM program. These revisions enhance organizations' preparedness for and response to disasters and emergencies. Similar to the changes previously made for hospitals and critical access hospitals, many existing elements were removed, and new standards were introduced. Consequently, the first half of the EM chapter applies to all programs except Critical Access Hospitals (CAH) and Home Care (OME). In contrast, the second half explicitly addresses CAH, HAP, and OME.


All programs and chapters have replaced the term "licensed independent practitioner" with more specific terms like "physician," "provider," or "staff member," as applicable. The environment of care (EC) chapter has undergone major updates, including removing redundant EPs related to smoking, merging EPs on system maintenance, and combining EPs on reporting and investigating incidents. This streamlining of the standards is a positive development. Additionally, several EP’s now address specific National Fire Protection Association (NFPA) 99 expectations, and updated references were incorporated where necessary. In the LS chapter, a redundant EP concerning NFPA revisions was removed to simplify the content further.

The life safety chapter describes the measures that must be taken to protect occupants from fire dangers. These standards emphasize the importance of a fire-safe environment and buildings, providing security. Conversely, the Environment of Care chapter addresses managing a safe environment and ensuring comprehensive safety measures.


The Joint Commission has identified several standards related to environment of care and life safety that have frequently been found to be non-compliant during surveys over the past few years.    


The frequent hot spots are the following:


  1. Hazardous Materials/Waste Management: EC.02.02.01 addresses risks associated with substances that, if released, would harm people or the environment. Examples include radioactive materials, hazardous chemicals, energy sources, medications, gases, and vapors. The predominant noncompliance concerns the availability, placement, or maintenance of eye washes.
  2. Utility Systems: EC.02.05.01 addresses inspection and testing of utility operating components, control of airborne contaminants, proper temperature, pressure, and humidity in critical environments, and management of disruptions. Risks in this area include electrical water, medical gas, vacuum, heating, ventilation, and air-conditioning systems, including potential failures. The majority of problematic issues stem from managing airflows (pressure relationships in critical locations) and labeling utility systems (mostly breaker panels).
  3. Means of Egress: LS.02.01.20 addresses the means of egress or escape, including the design of space, travel distance, egress illumination, and signage. 
  4. The Built Environment (Physical Environment): EC.02.06.01 addresses general findings in the physical environment and addresses cleanliness, repairs needed for equipment, patient care equipment such as beds, mattresses, ice machines, significant damage exposing sheetrock in patient care areas such as the operating room. 
  5. Fire Protection: EC standards 02.03.01, 02.03.03, and 02.03.05 address risks from fire, smoke, and other products of combustion and the responsibilities of managing a safe environment. Examples include identifying fire risks, preparing fire response plans, conducting fire drills, understanding the designation and use of smoke compartments, in addition to managing and maintaining fire detection and suppression equipment and systems and other safety equipment such as extinguishers, dampers, fire doors, etc. We often see deficiencies in fire drills not following a ninety day cycle, being completed too close together from drill-to-drill as to the time of day. Regarding equipment - the biggest issues are not resolving deficiencies timely or incomplete testing. 
  6. General Building Requirements: LS.02.01.10 addresses general life safety design, building construction, firewalls, and doors.
  7. Life Safety Protection: LS.02.01.30 addresses protection provided by built elements to protect occupants from smoke, such as smoke door features, windows, corridors, smoke barriers, and interior finishes.
  8. Automated Suppression Systems: LS.02.01.35 addresses suppression of fires, including sprinkler systems and portable fire extinguishers. This is where we find both the 18” sprinkler rule issue with storage too close to the sprinkler or ceiling, and the items being supported by sprinkler piping.


Because compliance with Joint Commission EC, EM, and LS standards can significantly impact patient safety, it should be consistently high and continuously monitored. When collaborating with the clinical tracer team, consider implementing a mock survey tracer program involving the physical environment. The document review and the building tour are only parts of the overall survey process. The clinical survey team is very knowledgeable regarding the physical environment and will site problematic observations during their clinical tracers.


Until next time,

 

Harold

Information for You

  1. CDC Recommended Vaccine Update Learn More
  2. FDA - Reprocessing Single-Use Medical Devices Learn More
  3. ISMP - Acute Care Alert Learn More
  4. JC FAQ Dialysis Wall Boxes Learn More
  5. JC FAQ ILSM Learn More
  6. JC FAQ Informed Consent Learn More
  7. JC FAQ Means of Egress Learn More
  8. JC FAQ Plant Operations Competencies Learn More
  9. JC FAQ Preconstruction Risk Assessment Learn More
  10. Red Cross - Critical Blood Shortage Learn More


We would love to hear from you!


We can help support your organization.

For consultations, education, and training, please contact us.

Visit Our Website
Contact Us
Join Our Email List