When specifying the Grundfos Magna3 pump, it is important to note that the pump has digital inputs that should be utilized when commanding the pump to start/stop.
Unlike a traditional fixed speed pump, starting and stopping the Magna3 should not be done via energizing or de-energizing the pump. Instead, line voltage should remain constant and the dedicated start/stop contacts should be utilized. The Magna3 should not be power cycled more than 4 times an hour to prevent damage to the control board.
The start/stop contacts are dry contacts and should never have any voltage applied to them; a field provided relay, such as a RIB Relay, should be used as necessary.
When paired with a Lochinvar boiler, the “Boiler Pump Output Contacts” on the boiler are wired to the start/stop contacts on the pump (a relay may be required in some applications). For typical HVAC applications, a Building Management System can be wired to the start/stop contacts. In a domestic hot water re-circulation setup, an aquastat is no longer needed as the Magna3 has a built-in temperature sensor. But, if you choose to utilize an aquastat anyway, it should be wired to the start/stop contacts and not the line voltage to the pump.
|